Customizing Conpot for Realistic ICS Emulation

The Problem with Default Templates

Conpot’s default template emulates an S7-200 PLC with whimsical configuration values clearly designed for demonstration purposes rather than realism. Examining the default template.xml reveals:

 1
 2
 3
 4
 5
 6
 7
 8
 9
10
<entity name="unit">S7-200</entity>
<key name="FacilityName">
    <value type="value">"Mouser Factory"</value>
</key>
<key name="SystemName">
    <value type="value">"Technodrome"</value>
</key>
<key name="sysLocation">
    <value type="value">"Venus"</value>
</key>

While functional for basic honeypot deployment, these values present several issues for research purposes:

  1. Obvious honeypot indicators: “Technodrome” and “Venus” are clearly not legitimate facility names
  2. Outdated hardware: S7-200 PLCs reached end-of-life in 2009, though they remain in use
  3. Generic configuration: No context suggesting actual industrial application
  4. Random register values: Modbus/S7comm registers contain randomized data rather than plausible sensor readings

For my research into attacker behavior against building automation systems, I needed something more convincing: a deployment that would pass initial scrutiny from experienced ICS security researchers or sophisticated threat actors.

Research-Driven Customization

My OSINT research using Shodan revealed patterns in real exposed Siemens deployments:

  • S7-1200 series dominance: The 1200 series represents current-generation PLCs commonly found in building automation
  • Realistic naming conventions: System names often reference function (HVAC, chiller, boiler) and location
  • Facility context: Building automation controllers typically identify mechanical spaces (basement, roof, equipment rooms)
  • Proper model numbers: Real systems expose legitimate Siemens order codes and firmware versions

These observations informed my customization strategy: create a honeypot that mirrors actual building automation deployments while maintaining the logging and monitoring capabilities essential for research.

Template Architecture Deep Dive

Understanding Conpot’s Template System

Conpot organizes templates as directory structures containing protocol-specific configuration files. Each template directory includes:

templtsmhs[ae7otnotmcdtmtepobpph_lmsumi/senam7snnrat/cddmmebeppe.mux.rxms.xom..hmtlxxtlommmclllols]#####SMWSC7oeNodbMrpbPeruiosnOsttIyoreDscertogfteliarmscerteeieedsrepnomtnaisptepysinagnsddatabuskeys

The template.xml file defines a “databus” - a key-value store that other protocol handlers reference. This architecture allows changing device identity in one place while having those changes propagate across all protocol implementations.

Key Configuration Files

template.xml: Defines system-wide identity s7comm/s7comm.xml: Controls responses to Siemens S7 protocol queries
modbus/modbus.xml: Maps Modbus registers to databus values

Understanding this separation is crucial: you modify device identity in template.xml, but protocol behavior in protocol-specific files.

Building a Realistic S7-1200 HVAC Controller

Device Identity Customization

Based on Shodan reconnaissance of real systems, I configured the template to present as a Siemens S7-1200 CPU 1214C in a building automation role:

1
2
3
4
5
6
7
<template>
    <entity name="unit">S7-1200</entity>
    <entity name="vendor">Siemens</entity>
    <entity name="description">Siemens S7-1200 PLC - Building Automation System</entity>
    <entity name="protocols">HTTP, MODBUS, s7comm, SNMP</entity>
    <entity name="creator">Building Management System</entity>
</template>

Critical databus values were updated to reflect a realistic deployment:

 1
 2
 3
 4
 5
 6
 7
 8
 9
10
11
12
13
14
15
<key name="FacilityName">
    <value type="value">"Central Heating Plant"</value>
</key>
<key name="SystemName">
    <value type="value">"HVAC-Controller-01"</value>
</key>
<key name="SystemDescription">
    <value type="value">"Siemens, SIMATIC, S7-1200, CPU 1214C DC/DC/DC"</value>
</key>
<key name="sysContact">
    <value type="value">"sys-help@blue-corvus.local"</value>
</key>
<key name="sysLocation">
    <value type="value">"Basement - Mechanical Room B2"</value>
</key>

The order code was set to a legitimate S7-1200 part number:

1
2
3
4
5
6
<key name="s7_id">
    <value type="value">"6ES7214-1AG40-0XB0"</value>
</key>
<key name="s7_module_type">
    <value type="value">"CPU 1214C DC/DC/DC"</value>
</key>

These values were chosen based on actual Siemens naming conventions and part numbering schemes, ensuring they would validate correctly against Siemens documentation if an attacker conducted verification.

S7comm Protocol Responses

The S7comm protocol implementation required updates to match the S7-1200 hardware profile. The default template’s s7comm.xml had incomplete module identification fields that I populated with realistic values:

 1
 2
 3
 4
 5
 6
 7
 8
 9
10
11
12
13
14
15
16
17
18
<s7comm enabled="True" host="0.0.0.0" port="102">
    <system_status_lists>
        <ssl id="W#16#xy1C" name="Component Identification">
            <system_name id="W#16#0001">SystemName</system_name>
            <module_name id="W#16#0002">SystemDescription</module_name>
            <plant_ident id="W#16#0003">FacilityName</plant_ident>
            <copyright id="W#16#0004">Copyright</copyright>
            <serial id="W#16#0005">s7_id</serial>
            <module_type_name id="W#16#0007">s7_module_type</module_type_name>
            <location id="W#16#000B">sysLocation</location>
        </ssl>
        <ssl id="W#16#xy11" name="Module Identification">
            <module_identification id="W#16#0001">6ES7214-1AG40-0XB0</module_identification>
            <hardware_identification id="W#16#0006">V4.2</hardware_identification>
            <firmware_identification id="W#16#0007">V4.2.3</firmware_identification>
        </ssl>
    </system_status_lists>
</s7comm>

Note the firmware version V4.2.3 - this corresponds to a legitimate S7-1200 firmware release, making the system appear authentic to fingerprinting tools like snap7 or s7scan.

The port was also corrected from 10201 to the standard S7comm port 102, ensuring the honeypot matches expected protocol behavior.

Modbus Register Configuration

The default Modbus configuration used random binary values for registers, which would appear suspicious during reconnaissance. Real HVAC systems expose sensor readings, setpoints, and equipment status in specific value ranges.

I reconfigured the analog input registers to simulate realistic HVAC telemetry:

1
2
3
4
5
6
7
8
<key name="memoryModbusSlave2BlockC">
    <!-- ANALOG_INPUTS: HVAC sensor readings -->
    <value type="value">[220, 185, 650, 420, 850, 1050, 730, 0]</value>
</key>
<key name="memoryModbusSlave2BlockD">
    <!-- HOLDING_REGISTERS: HVAC setpoints -->
    <value type="value">[210, 200, 500, 400, 800, 1000, 750, 0]</value>
</key>

These values, when interpreted with appropriate scaling factors, represent:

  • 220: 22.0°C supply air temperature
  • 185: 18.5°C return air temperature
  • 650: 6.5 bar chilled water pressure
  • 420: 42% damper position
  • 850: 85% pump speed
  • 1050: 10.5 m³/min flow rate
  • 730: 73% humidity

Values remain static (unlike a real system with fluctuating sensors) but fall within plausible operational ranges for commercial HVAC equipment.

The Modbus device info was also updated:

1
2
3
4
5
<device_info>
    <VendorName>Siemens</VendorName>
    <ProductCode>SIMATIC S7-1200</ProductCode>
    <MajorMinorRevision>V4.2.3</MajorMinorRevision>
</device_info>

Docker Build Process

Template Path Discovery

Implementing these customizations required building a custom Docker image. The first challenge: determining where Conpot actually stores its templates inside the container.

The base image path wasn’t documented clearly, requiring inspection:

1
docker run --rm honeynet/conpot:latest find / -name "template.xml" 2>/dev/null

This revealed templates reside at:

/home/conpot/.local/lib/python3.6/site-packages/conpot-0.6.0-py3.6.egg/conpot/templates/

A significantly different path than the /usr/src/conpot/conpot/templates/ location suggested in some documentation.

Custom Image Creation

With the correct path identified, I created a Dockerfile to overlay my customized template:

1
2
3
4
5
6
7
FROM honeynet/conpot:latest

# Copy custom template to correct location
COPY templates/custom/default /home/conpot/.local/lib/python3.6/site-packages/conpot-0.6.0-py3.6.egg/conpot/templates/custom

# Expose standard ICS ports
EXPOSE 80 102 502 161/udp

The directory structure required careful attention - Conpot expects template files directly under the template name directory, not nested in a subdirectory.

Building the image:

1
docker build -t conpot-hvac:latest .

Deployment Challenges

Initial deployment attempts failed with “Template not found: custom” errors. Troubleshooting revealed several issues:

Problem 1: Incorrect ENTRYPOINT syntax

The base image uses a specific entrypoint that couldn’t be overridden with simplified commands. Inspection revealed:

1
2
docker inspect honeynet/conpot:latest --format='{{.Config.Cmd}}'
# Output: [/home/conpot/.local/bin/conpot --template default ...]

Solution: Use complete command path in docker-compose:

1
2
command: ["/home/conpot/.local/bin/conpot", "--template", "custom", 
          "--logfile", "/var/log/conpot/conpot.log", "-f", "--temp_dir", "/tmp"]

Problem 2: Port mapping discrepancies

Conpot runs services on non-standard internal ports that must be mapped to standard external ports:

  • HTTP runs internally on 8800 → external 80
  • Modbus runs internally on 5020 → external 502
  • S7comm runs internally on 102 → external 102 (correctly configured)
  • SNMP runs internally on 16100 → external 161

Docker-compose configuration:

1
2
3
4
5
ports:
  - "80:8800"         # HTTP
  - "102:102"         # S7comm
  - "502:5020"        # Modbus
  - "161:16100/udp"   # SNMP

Verification and Testing

With the customized honeypot deployed, verification confirmed proper operation:

HTTP Interface:

1
2
curl http://localhost:80
# Returns: HVAC-Controller-01 status page

Log Output:

222222000000222222666666------000000111111------222222666666222222222222::::::111111000000::::::444444777777,,,,,,011111522777726456SCCMSHtooo7TanndCTrppboPtooumittsmsnegmSssro7eevCdCrreobovvrnumeepsmrrsottiissannttruiiaatsttrreiiittdnaaeegllddoiintzzoo:eeennmdd::p'l0a''.t000e...:000...000..'00,/''t,,8e8m510p000l22)a0)t)es/custom

All protocols initialized successfully with the custom configuration loaded.

S7comm Fingerprinting (when performed by attackers) will now return:

  • Model: CPU 1214C DC/DC/DC
  • Serial: 6ES7214-1AG40-0XB0
  • Firmware: V4.2.3
  • Location: Basement - Mechanical Room B2
  • System: HVAC-Controller-01

These values match real Siemens deployments observed via Shodan, significantly improving the honeypot’s plausibility.

Why These Details Matter

The investment in creating a realistic template serves several research objectives:

1. Attracting sophisticated actors: Generic honeypots may be ignored by experienced attackers who quickly identify obvious deception. A convincing configuration is more likely to attract serious reconnaissance activity.

2. Understanding attacker validation: By providing legitimate-looking model numbers and firmware versions, I can observe whether attackers validate these details against vendor documentation - indicating more sophisticated tradecraft.

3. Behavioral authenticity: Realistic Modbus register values may encourage attackers to proceed with exploitation attempts, whereas random data might trigger suspicion.

4. Comparative analysis: With both the default “Technodrome” and this customized deployment, I can compare which attracts more attention and what types of interaction occur with each.

5. Building automation targeting: This specific configuration allows research into attacks targeting building management systems, an increasingly concerning attack surface as smart buildings proliferate.


Next research phases:

  1. Comparative analysis: Monitor interaction patterns between default and customized deployments
  2. Log aggregation: Implement Grafana + Loki stack for centralized log analysis (guide prepared separately)
  3. Behavioral documentation: Track how attackers interact with realistic vs. generic configurations
  4. Temporal analysis: Identify patterns in when attacks occur and from which geographic regions
  5. Protocol exploitation: Document specific S7comm and Modbus exploit attempts

Technical Resources:

Configuration files referenced in this post:

  • template.xml: Core device identity and databus configuration
  • s7comm/s7comm.xml: S7 protocol response definitions
  • modbus/modbus.xml: Modbus register mappings
  • Dockerfile: Custom image build instructions
  • docker-compose.yml: Deployment orchestration

This research continues as part of my MSc in Information Security at Royal Holloway, University of London, investigating threat landscapes facing industrial control systems and building automation infrastructure.

 

Corvus

Security research, tools, development projects, and CTF write-ups by Nicholas Coleman (independent security researcher, MSc. Information Security).


Building a believable HVAC controller honeypot